Switch Gear & protection
Chapter-03
(Busbar arrangement)
    -Asiqur Rahman Milon,EETE-DIU,EEE-IEB(Con)
#What is Bus bar?
-Bus bar-
An electrical bus bar is defined as a conductor or a group of conductor used for collecting electric power from the incoming feeders and distributes them to the outgoing feeders. In other words, it is a type of electrical junction in which all the incoming and outgoing electrical current meets. Thus, the electrical bus bar collects the electric power at one location.( A bus – bar is a conductor or group of conductors and it collects electric energy from incoming feeders and distributes them to outgoing feeders. So bus – bar is a junction where all incoming and outgoing currents meet. Bus – bar is generally made up of aluminum but not with copper because aluminum has special characters like higher conductivity, lower cost, excellent corrosion resistance, etc.)
The bus bar system consists the isolator and the circuit breaker. On the occurrence of a fault, the circuit breaker is tripped off and the faulty section of the busbar is easily disconnected from the circuit.
The electrical bus bar is available in rectangular, cross-sectional, round and many other shapes. The rectangular bus bar is mostly used in the power system. The copper and aluminium are used for the manufacturing of the electrical bus bar.
electrical-bus-barsThe most common of the bus-bars are 40×4mm (160 mm2); 40×5 mm (200 mm2) ; 50×6 mm (300mm2) ; 60×8 mm (480 mm2) ; 80×8 (640 mm2) and 100×10 mm (1000 mm2).
The various types of busbar arrangement are used in the power system. The selection of the bus bar is depended on the different factor likes reliability, flexibility, cost etc. The following are the electrical considerations governing the selection of any one particular arrangement.
·       The bus bar arrangement is simple and easy in maintenance.
·       The maintenance of the system did not affect their continuity.
·       The installation of the bus bar is cheap.
The small substation where continuity of the supply is not essential uses the single bus bar. But in a large substation, the additional busbar is used in the system so that the interruption does not occur in their supply. The different type of electrical busbar arrangement is shown in the figure below.
# What is the properties of bus bar?
We have different types of bus – bar arrangements we need to choose the required arrangement. This depends on various factors such as
1. System voltage.
2. Position of a substation in the system.
3. Reliability of supply.
4. Flexibility.
5. cost.
6. Availability of alternative arrangements if outage of any of the apparatus happens.
7. Bus – bar arrangement should be simple and easy to maintain.
8. In case of load – growth there must be the possibility to extend the system to meet the load requirements.
9. The installation should be as economical as possible, keeping in view about the needs and continuity of supply.

#What is the shape and structure of bus bar?
-The bus bar shape generally is rectangular shape,square shape,triangle shape.It’s each height is 2m to 5m.In a bar or in a section interconnected by clamp,nut bolt,welding etc.In a bus bar one side is use for accept supply and another side is used for supply distribution to various load circuit.

#Describe different types of Bus bar?
-The different types of bus bar is-
1) Indoor bus bar
2) Outdoor bus bar
3) Open bus bar
4) Enclosed bus bar
5) Oil sinking bus bar
6) Pressured gas insulated bus bar
7) With 3-phase bus bar
8) Without 3-phase bus bar
9) Isolated phase bus bar

#Mention different types of bus bar arrangement?
-The bus bar arrangement is given below-
1. Single bus-bar arrangement.
2. The single bus-bar arrangement with bus sectionalized.
3.Double bus arrangement.
4. Double bus double breaker arrangement.
5. One and a half Breaker arrangement.
6. Main and transfer bus arrangement.
7. Double bus system with by pass isolators.
8. Ring main arrangement.
9. Mesh arrangement.

#Describe single busbar arrangement with application and advantages and dis advantages?
- Single busbar arrangement with application and advantages and dis advantages is-
1.    Single Bus-Bar Arrangement
It is a simplest form of arrangement of bus-bar. It is used in power stations and small outdoor substations having small number of incoming and outgoing feeders. Each generator and feeder is controlled by a circuit breaker.
single bus-bar arrangements
Advantages
It has low initial cost.
It required less maintenance.
Simple operation.
Disadvantages
If fault occurs on bus-bar, whole supply is affected.
For repair and maintenance of the bus-bar, whole of the system has need to be de-energized.

# Sectionalized single busbar arrangement with application and advantages and dis advantages?
- Single busbar arrangement with aplication and advantages and dis advantages is-
Single Bus-Bar Arrangement with Sectionalization
In large power generating stations, where several numbers of generators and feeders are required to be connected to the bus-bar. In that cases, Single bus-bar arrangement with sectionalization is employed. Normally the number of sections of a bus-bar is 2 to 3 in generating station and substation.
http://www.apseee.com/wp-content/uploads/2017/04/2-9-993x1024.jpg


Advantages
1.    In case, when fault occurs on any section faulty section can be disconnected without affecting other section.
2.    This arrangement is more reliable that single bus-bar arrangement.
3.    The repair and maintenance of any section of the bus-bar can be carried out be disconnecting that section only.
4.    Future extension is possible in this arrangement.
Disadvantages
In this arrangement additional circuit breakers and isolators are required for sectionalisation. Hence, cost is increased.





# Ring busbar arrangement with application and advantages and dis advantages?
- Ring busbar arrangement with application and advantages and dis advantages-
Ring Bus-Bar Arrangement
In this arrangement, each feeder is supplied from two paths. This is an extension of the sectionalized arrangement.
http://www.apseee.com/wp-content/uploads/2017/04/3-6-852x1024.jpg
Advantages
This arrangement provides greater flexibility. In case, fault occurs , it does not affects the other section.
The number of circuit breaker required in this arrangement almost same as in a single phase bus-bar system. It reduces the initial cost.
Disadvantages
Extension is not possible in this arrangements. Separately protection system is required for each circuit.

Main and Transfer Bus-Bar Arrangements
Such a arrangement consists of two bus-bars a “main bus-bar” and “an auxiliary bus-bar. This arrangement is adopted where continuity of supply. Each generator and feeder may be connected to either bus-bar with the help of bus coupler which consists of a circuit breaker and isolating switches.
http://www.apseee.com/wp-content/uploads/2017/04/4-2-1024x803.jpg
Advantages
If fault occurs on the bus-bar, supply can be maintained by transferring it to the healthy.
The other feeders can be connected to the bus-bars without disturbing the existing system.

Mesh arrangement:
In mesh arrangement between the mesh formed by bus bars circuit breakers are installed as shown in the following figure:
Electrical Bus
From the node point of mesh, the circuit is tapped. We need to open two circuit breakers when the fault occurs so that protection can be obtained but switching is not possible.
Advantages of mesh system:
1. Provides protection against the fault.
2. For substations having a large number of circuits, this arrangement is suitable.
Disadvantages of mesh system:
1. It doesn’t provide switching facility.
2. Not suitable for all type of substations.


Double bus arrangement:
Double bus arrangement has two bus bars and the incoming feeders and outgoing feeders are connected in parallel to both buses with the help of isolators. By closing the isolator switch we can connect the feeders either to bus – bar 1 or to bus – bar 2. We can divide the load among two buses with the help of isolator switches by closing the isolator switch that is connected to bus – bar 1 and feeder the load can be connected to bus – bar 1 and by closing the isolator switch connected to bus – bar 2 and feeder the load gets connected to bus – bar 2.  This can be shown in the following figure:
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEhDmckRKqGe5J5Yx0m9n7wTlexgtyO4JRoQt6THNTStFpTUS_-NTk7WXm2dVSqeGEC-hr5Ag8DCvaSIZE3QKesDOgGBZKaL2rO5VE6wxrrbfwn6auTt-DkPpWcUD7cDfKwu8oo46KqnuGYQ/s640/Capture.JPG
We have a bus coupler breaker which is used for bus transfer operation. When we need to transfer load from one bus to another bus we need to close the bus coupler first and then close isolators of the associated bus to which load is to be connected and open the isolator switch coupled to fault bus and then open the bus coupler breaker.
Advantages of double bus system:
1. It has greater flexibility.
2. During fault conditions, there is no interruption of power supply to the load.
Disadvantages of double bus system:
1. We cannot transfer load from one bus to another bus without interruption of power supply for few minutes.
Double bus double breaker arrangement:
In double bus double  breaker arrangement we connect a feeder in parallel to both buses with the help of two circuit breakers and isolator switches instead of bus coupler as shown in the following figure:
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEiWRcfSTK3lwxsOC7-ThT0tKsZPhNdWxrnVhF0L9b0oGsZvAt4-QzlfvEE34CMqMgLXW11Xya0ZGUeovuyukk6pU4lGGaBXaOJdQRG23IGCBxJyjhbRftCayYWIMSp7n6Oyrnqy_0r-miv7/s640/Capture.JPG
Here we energize both the feeders and divide feeders among both the buses but we can connect the desired feeder to the desired bus at any time for this purpose we need to close the isolator and then circuit breaker associated with the required bus – bar and later open the circuit breaker and then isolator from which it has to be disconnected.
Advantages of double bus double breaker system:
1. During fault conditions, the load can be transferred to one bus so there will not be an interruption in power supply.
2. Here we are not using a bus coupler so there will not be much delay in power supply while closing circuit breaker to transfer load from one bus to another bus.
3. High flexibility.
Disadvantages of double bus double breaker system:
1. The number of circuit breakers used is high so cost is very high.
2. Maintenance cost will also be high.
So this type of arrangement is used very rarely.
One and a half breaker arrangement:
Because of the high cost of double bus double breaker arrangement we use one and a half breaker arrangement. Here the two feeders are fed through their corresponding bus – bars and these two feeders are coupled by a third circuit breaker called tiebreaker as shown in the following figure:
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEgaW4Q61klnXJ7W4wwcLxwD6gNBT_E4V_XhqZ6wQyn9ctJh-BetzmUgKYLJnAaK762Jx7v_T-07wei5_Krk349_WDEIvCM_i5AikN0J3IYUUqmraz9M6mqjiQ9t2L_hZhjJOa-76WBr2you/s400/Capture.JPG
During normal conditions, all the three circuit breakers are closed and both circuits operate in parallel and power is fed to feeders from the two bus – bars. If the fault occurs on one bus bar then with the help of the second bus – bar feeder circuit breaker and tiebreaker power are fed to feeders. This means each feeder breaker has to be rated to feed both feeders which are coupled by tiebreaker.
Advantages of one and a half breaker system:
1. There will be no interruption of power in case of fault because all the feeders can be transferred to another healthy bus immediately.
2.  Additional circuits can be easily added to the system.
3. Cost is less compared to double bus double breaker arrangement.
Disadvantages of one and a half breaker system:
1. This arrangement is complicated because during fault two circuit breakers are to be opened.
2. Maintenance cost is high.


#why do sectionalized in a bus bar?
In this scheme, the main bus is sectionalized by a bus coupler breaker & two nos. isolators by which the main busbar can be done separately as when required. The shutdown of one portion of the busbar can be taken for any maintenance work purpose. It is shown in the below fig.


http://www.electricalunits.com/Image/power-system/secsinglebusbar.png


The advantage & disadvantage of sectionalized single bus system is given below:-

Advantage:

  1. The operation of this system is a simple as that of the single busbar system.
  2. Maintenance cost is low.
  3. For maintenance or repairing of the busbar, only one-half of the busbar is required to be de-energized, hence the possibility of a complete shutdown is thereby avoided.
  4. It is possible to utilize the busbar potential for the line relays.


Disadvantage:

  1. The main disadvantage, when a circuit breaker of any circuit of this system fails, power can not be given the said circuit until rectification of the circuit breaker.
  2. For regular maintenance work at busbar, one of half busbar is required to be de-energized, hence feeders & transformer of that portion will be kept in off condition.
  3. If at any stage, a circuit is required to be added to the existing system, half of the busbar is to be de-energized during the period the work is carried out.

Switching Schemes:

Switching schemes implies different methods employed to connect electrical circuits in the power system to transfer the electrical power in reliable manner. Switching schemes helps in deliver the electrical power to power system if any part of the system is faulty or under maintenance.
Substations use different types of busbar arrangements or switching schemes depends upon the application, reliability of the supply and cost of installation. In every substations busbars plays a common role to connect different circuits. However switching is possible in the power system with the help of circuit breakers and isolators.

Considerations for selection of busbar arrangement:

Different types of busbar arrangements are employed based on the voltage, reliability of the supply, flexibility in transmitting power and cost. The other aspects considering in designing the busbars arrangements are:
1.    Simplicity in the design
2.    Maintenance of different elements without interruption in the power supply
3.    Future expansion feasibility
4.    Economical in cost of installation and operation