Switch Gear & protection
Chapter-02
(The concepts of electrical faults)
-Asiqur Rahman Milon,EETE-DIU,EEE-IEB(Con)
#What is electrical faults?
- Fault in electrical equipment or
apparatus is defined as an imperfection in the electrical circuit due to which
current is deflected from the intended path. In other words, the fault is the
abnormal condition of the electrical system which damages the electrical
equipment and disturbs the normal flow of the electric current.
#What is the name of different types of faults in
electrical power system?
- Types of Faults in Power
System
The
fault in the power system is
defined as the defect in the power system due to which the current is
distracted from the intended path. The fault creates the abnormal condition
which reduces the insulation strength between the conductors. The reduction in
insulation causes excessive damage to the system. The fault in the power
system is mainly categorised into two types they are
1.
Open Circuit Fault
2.
Short Circuit Fault.
The
different types of power system fault are shown below in the image.
The
faults in the power system may occur because of the number of natural
disturbances like lightning, high-speed winds, earthquake, etc. It may also
occur because of some accidents like falling off a tree, vehicle colliding,
with supporting structure, aeroplane crashing, etc.
1. Open Circuit Fault
The
open circuit fault mainly occurs because of the failure of one or two
conductors. The open circuit fault takes place in series with the line, and
because of this, it is also called the series fault. Such types of faults
affect the reliability of the system. The open circuit fault is categorised
as
·
Open Conductor Fault
·
Two conductors Open Fault
·
Three conductors Open Fault.
The
open circuit fault is shown in the figure below.
2. Short-Circuit Fault
In
this type of fault, the conductors of the different phases come into contact
with each other with a power line, power transformer or any other circuit
element due to which the large current flow in one or two phases of the system.
The short-circuit fault is divided into the symmetrical and unsymmetrical
fault.
Symmetrical Fault
The
faults which involve all the three phases is known as the symmetrical fault.
Such types of fault remain balanced even after the fault. The symmetrical
faults mainly occur at the terminal of the generators. The fault on the system
may arise on account of the resistance of the arc between the conductors or due
to the lower footing resistance. The symmetrical fault is sub-categorized into
line-to-line-to-line fault and three-phase line-to-ground-fault
a. Line – Line – Line Fault – Such
types of faults are balanced, i.e., the system remains symmetrical even after
the fault. The L – L – L fault occurs rarely, but it is the most severe type of
fault which involves the largest current. This large current is used for
determining the rating of the circuit breaker.
b. L – L – L – G (Three-phase line to the ground
fault) – The three-phase line to ground fault includes all the
three phase of the system. The L – L – L – G fault occurs between the three
phases and the ground of the system. The probability of occurrence of such type
of fault is nearly 2 to 3 percent.
Unsymmetrical Fault
The
fault gives rise to unsymmetrical current, i.e., current differing in magnitude
and phases in the three phases of the power system are known as the
unsymmetrical fault. It is also defined as the fault which involves the one or
two phases such as L- G, L – L, L – L – G fault. The unsymmetrical makes the
system unbalanced. It is mainly classified into three types. They are
1.
Single Line-to-ground (L – G) Fault
2.
Line-to-Line Fault (L – L)
3.
Double Line-to-ground (L – L – G) Fault
The
unsymmetrical fault is the most common types of fault occur in the power
system.
1. Single Line-to-Line Ground – The single line of ground fault occurs when one
conductor falls to the ground or contact the neutral conductor. The 70 – 80
percent of the fault in the power system is the single line-to-ground fault.
2. Line – to – Line Fault – A line-to-line fault occurs when two
conductors are short circuited. The major cause of this type of fault is the
heavy wind. The heavy wind swinging the line conductors which may touch
together and hence cause short-circuit. The percentage of such type of faults
is approximately 15 – 20%.
3. Double Line – to – line Ground Fault – In double line-to-ground fault, the two lines
come in contact with each other along with the ground. The probability of such
types of faults is nearly 10 %.
The
symmetrical and unsymmetrical fault mainly occurs in the terminal of the
generator, and the open circuit and short circuit fault occur on the transmission line.
#What
are the causes of faults in Electrical power system?
- The causes
of faults in Electrical power system are-
1. Grid
failure : This may happen due to sudden tripping a bulk source of power like
Power station, upstream transformer, up stream transmission line or
malfunctioning of upstream circuit breaker. These may happen due to Power
station internal problems, uncontrolled power power management at RLDC
(Regional Load Dispatch Center), Thunder Storm etc.
2. Local
Power System Failure: Failure of Power / Distribution transformer, Transmission
and Distribution Line , Power Cable ( Normally HT cable of medium and high
voltage grade).
Basic
System fault for tripping of interrupter ( circuit breakers) are;
1. Normal
over current Tripping
2. INSTANTANEOUS
OVER CURRENT or SHORT CIRCUIT FAULT
3. EARTH
FAULT or INSTANTANEOUS EARTH FAULTS.
- Abnormal
condition (Like Overloading or inrush current)
- Relay
and Circuit Breaker co-ordination delay or no co-ordination
6. Insulation
failure
7. Lighting
surge
8. Voltage
drop
9. Unbalance
and stability collapse Etc.
0 Comments